DSC Classic PC1555 - 8 Zone Hybrid Wireless Security System 

8 Zone Hybrid Wireless 
Security System 

DSC Classic PC1555 
 
     Upto 12 Keypads 
  • up to 8 hardwired and 4 wireless keypads
  • 3 hardwired keypads available…
  • PC1555RKZ eight zone LED keypad with zone input 
    PC5508Z eight zone LED keypad with zone input 
    LCD5500Z alphanumeric keypad with zone input 
     
  • WLS910 - wireless hand-held keypad
  • added wireless control is provided by…
  • WLS908 - wireless panic pendant 
    WLS909 - wireless key 
     
     8Zones Hardwired or Wireless 
  • 6 programmable zones expandable to 8 zones using keypad zone inputsor wireless zones
  • Wireless 

  • PC5132 - wireless receiver module
  • connect up to 8 wireless zones 
 
  2 ProgrammableVoltage Outputs 
 
  • PGM1 and PGM2 with 24 programmable options 
     AdvancedCommunications 
  • supports all major formats including SIA and Contact ID
  • LINKS 1000 cellular communication
  • LINKS 2150 long range radio communication
  • DVACS using PC5400DV-SG in place of PC5400 printer module
  • event-initiated personal paging
  • 3 phone numbers (3rd backs up primary number)
  • 2 account numbers 
     EfficientInstallation 
  • 4 wire communications bus (KEYBUS) 
  • connect keypads and modules up to 1000' (330m) from controlpanel
     
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
.
ThePC1555 brings remarkable new technology and product design together ina system that is ideal for residential, commercial, and institutional applications.More than a burglar alarm, the PC1555 is a complete life safety and securitysystem offering the latest advances in hybrid wireless / hardwired burglaryand fire protection. 

While thePC1555 provides superior electronic protection of life and property, italso supplies a full range of system control options that can be fullycustomized to meet the exact requirements of the system owner. The PC1555not only offers a variety of wall mounted keypads and hand-held wirelesscontrollers, but each interface also provides fully customized operation. 

Exceptionalquality, complete design flexibility, fully customized system control,and the reliable peace-of-mind security your customers can count on foryears to come – it all adds up to the new PC1555 from DSC. 

·  P C 1 5 5 5   S e c u r i t y   S y s t e m  · 
 
PC1555 Main Control Panel
    8 fully programmable zones 
    6 hardwire zones on main control panel plus 2 keypad input zones
    all 8 zones hardwired orwireless using PC5132 wireless receiver
    all zones programmable as burglary or fire*
    zone wiring options include… Normally Closed, Single End of Line (EOL)resistor, and Double EOL resistor
      * keypad zones cannot be programmed as firezones if panel is programmed for Double EOL resistor supervision
    27 programmable zone types, 8 programmable zone attributes
     
  • 128 event buffer
  • all events automatically stored with time and date stamp to buffer
    events can be printed on-site, viewed through the LCD Keypad or DLSsoftware
  • alarm output
  • bell output - 700mA @ 12VDC, PTC protected
     
  • 2 programmable voltage outputs
  • -PGM1 ....  North America ....  low current, 50mA @12VDC
        International ....  high current, 300mA @12VDC
    -PGM2 ....  North America ....  high current, 300mA @12VDC
    (can also be used for 2 wiresmoke) 
        International ....  low current, 50mA @12VDC
     
    - 24 programmable options
     
  • local PCLINK™ and remote upload/download capability
  • - PCLINK allows direct connection of PC to alarm panel
    - program system using DLS software
    - view status and trouble conditions
    - view 128 event buffer
     
  • 1A regulated power supply
  • - auxiliary power… 12VDC, 550mA
    - positive temperature coefficient (PTC) AUX & Bell outputprotection
    - electronically protected from KEYBUS faults
    - supervision for AC power loss and low battery
    - internal clock locked to AC power frequency
     
  • battery required : 12V, 4Ah, rechargeable sealed lead-acid
  • transformer required : 16.5VAC, 40VA 
 

     SystemOperation 

  • 39 access codes
  • 32 user codes, 1 master code, 2 duress codes, 2 supervisorcodes, 1 installer code, and 1 maintenance code
    individual open/close reporting by user
     
  • ' no code required for Bypassing' option
  • allows users to bypass zones without entering an accesscode
     
  • 'quick arm' and 'quick exit'
  • allows users to arm and exit easily 
     
  • 'stay/away' zones and 'stay'arming
  • security of perimeter arming while premise is occupied
     
  • automatic arming
  • program system to auto-arm at aspecific time every day
     
  • 'activity delinquency'code
  • signals monitoring station if no activity is sensed in premisefor a programmable period of time
     
  • door chime
  • programmable by zone
    monitor a door by having keypad beep when the door is openedor closed
     
Wireless Security 
PC5132Wireless Receiver 
PC5132 Wireless Receiver
 
  • connect up to 8 Marquis™  wireless detectors
  • true 'Spread Spectrum' technology, 900 MHz, fully supervised for communicationintegrity
  • 12 minute supervisory time
  • connect to 4 wire KEYBUS up to 1000' (330m) from control panel
  • current draw : 125mA 
     WirelessControl Devices 

 Wireless Control Devices 
 

  • WLS908 Wireless Panic Pendant
  • communicates a non-medical alarm to central station
    8 pendants maximum 
    ...each occupying 1 zone
    sealed non-replaceable battery
     
  • WLS909 Wireless Key
  • remote arm/disarm control
    up to 16 keys per system
    3 photo/electronic 1.5V batteries included
     
  • WLS910 Wireless Hand-Held Keypad
  • personal remote keypad
    up to 4 wireless keypads per system 
    (in addition to hardwired keypads)
    3 'AAA' batteries included
     
       PC5400- RS232 
    Serial Printer Interface Module 
  • allows serial printer connection for reportof events logged to the PC1555event buffer
  • supports any 300, 1200, 2400 or 4800 BPS serial printer
  • multiple languages available
  • module connects to 4 wire KEYBUS up to 1000' (330m) from control panel
  • c/w DB-25 modular connector for easy connection
  • current draw :65mA
  • maximum one module per system …PC5400DV-SG DVACS module may be substitutedfor full DVACS communications capability (see separate DVACS spec sheet) 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
. 
     FalseAlarm Prevention Features 
  • audible exit delay 
  • audible exit fault
  • arm/disarm bell squawk
  • urgency on entry delay
  • quick exit
  • programmable swinger shut down by zone
  • programmable transmission delay by zone
  • AC failure, TLM trouble, and Low Battery transmission delays
  • recent close code transmission
  • cross zone police code transmission
  • opening after alarm code transmission
      FullSupervision 
  Trouble conditions are displayed on all keypads and canalso be communicated to central station for :
 
  • battery trouble
  • AC failure
  • zone low battery 
  • auxiliary power trouble
  • zone tamper
  • zone fault
  • system tamper
  • fire trouble
  • siren circuit trouble
  • arming delinquency
  • general system trouble 
  • failure to communicate
  • event buffer 75% full 
  • loss of system time
  • telephone line trouble - (via LINKS™ cellular communicator)
  • general system supervisory trouble … reports when system fails tocommunicate with any module on the KEYBUS 
 

LED & LCD Keypads 
 

Plain LanguageLCD5500Z Keypad 
 

Plain Language LCD5500Z Keypad
  The PC1555 security system is fully programmable from theattractive, easy to use dual-language LCD5500Z keypad :
 
    connect up to 8 keypads, combination LED and/or LCD 
  • zone input
  • - connect detector to keypad to replace one of 6 main panelzones or increase total zones up to 8 with 2 keypads
     
  • dual-language

  • (languages vary according to country
    - simple key entry to toggle between languages while viewingkeypad
     
  • large 32 character display
  • - zone identification     - system instructions
    - system status           - 128 event buffer
    - trouble conditions
     
  • plain language operating instructions
  • - menu for user functions
    - what key to press for specific functions
    - steps for programming functions
     
  • 5 programmable function keys with 15 options such as Home Arm, AwayArm, Quick Exit etc.
  • 4 keypad-activated alarms : Fire, Auxiliary, Panic, and duress
  • 3 LED indicators : Ready, Armed and Trouble
  • - allow system status to be viewed at a glance
     
  • backlit display
  • - display and keys backlit for easy viewing in low light conditions
    - adjustable brightness and contrast
    - Backlighting Boostprovides extra high key lighting whenany key is pressed
     
  • piezo buzzer
  • - provides audible feedback for correct key entries, pre-alert,and system trouble status
    - select from 21 different buzzer tones
     
  • connect to 4 wire KEYBUS up to 1000' (330m) from control panel
  • specifications
  • - current draw : 90mA with backlighting boost
    - dimensions : 5.75" x 4.5" x 1" deep 
    (144 x 114 x 25mm) 
     
 

LED Keypads 
 

LED Keypads
      PC1555RKZ         PC5508Z
Two keypads are available… with zone input
PC1555RKZ … 8 zone LED keypad 
PC5508Z … 8 zone LED keypad 
  • zone input
  • - connect detector to keypad to replace one of 6 main panelzones or increase total zones up to 8 with 2 keypads 
     
  • 5 keypad functions with choice of 15 programmable options
  • - separate function keys on PC5508Z 
     
  • connect to 4 wire KEYBUS up to 1000'

  • (330m) from control panel
 
  • LED indicators:
PC1555RKZ.... Ready, Armed, System
  PC5508Z ....  Ready, Armed, Trouble, Memory, Bypass, Fire,Program
 
  • 4 keypad-activated alarms… Panic, Auxiliary, Fire, and Duress
  • backlit display…with Backlighting Boostto provide extra high keylighting when any key is pressed
  • piezo buzzer… provides audible feedback for correct key entries,pre-alert, and system trouble status
  • specifications : current draw

  • … 90mA with backlighting boost 
    - PC1555RKZ  
    ...5.5" W x 4.5" H x 1" D 
    (140 x 114 x 25mm) 
    - PC5508Z, LCD5500Z 
    ...5.75" W x 4.5" H x 1" D 
    (144 x 114 x 25mm) 
     
·  P C 1 5 5 5   S e c u r i t y   S y s t e m  · 
 
A rchitect'sSpecifications
...........................................................................................................................
 
The contractor shall provide a complete electrically supervised,battery backed-up, fire and burglary alarm system. The system shall becomplete with a multi-zone alarm system with the capacity of up to 8 burglaror Class B fire zones of which up to 8 may be wireless zones. All zonesshall be supervised and be capable of operating listed heat detectors,smoke detectors, alarm contacts, motion detectors, vibration detectorsand other listed fire and burglary alarm detection devices. The systemshall have 1 low current voltage output and 1 high current voltage output.All outputs shall be programmable to activate for 1 of 23 options. Systemshall be complete with a 4 wire unshielded (QUAD) communications bus thatallows system modules and keypads to be added anywhere on the bus up to1,000 feet (330m) per leg from the main control panel. Bus shall be ableto withstand temporary shorts of up to +12V without control panel damage.The system shall be capable of providing 550mA of 12VDC auxiliary powerfor alarm devices. 

The alarm panel shall be capable of digital communications via regulartelephone line, LINKS cellular, LINKS long range radio and DVACS to twoseparate monitoring stations or locations with 2 account numbers and 3telephone numbers. LINKS cellular communication shall be capable of backupor sole communications to monitoring stations and for upload/ downloadoperations. The system communicator shall be capable of communicating inall major formats including SIA and Contact ID. Events transmitted shallbe programmable to include: fire alarms, burglary alarms, trouble alarms,supervisory conditions, alarm restoral codes, opening (disarming) and closing(arming) codes, partial closing codes, and opening after alarm codes. Thesystem shall be capable of paging personnel on the occurrence of any ofthe above events selected by the owner. The system shall be capable oftransmitting a test code to the monitoring station(s) on a programmabledaily, weekly or monthly frequency at a regular time of day. 

There shall be a 700mA, PTC protected, supervised bell/siren circuitthat will drive a bell/siren until reset or silenced. Siren output shallbe programmable as steady or pulsed for each zone. 

The alarm panel shall be equipped with EEPROM memory to retain all programinformation even if all AC and battery power is lost and shall have integralstatic and lightning protection circuitry. 

To prevent false alarms and unnecessary transmissions to monitoringstations, the alarm panel shall have SIA false alarm prevention features,programmable swinger shut down by zone, audible exit delay, audible exitfault, opening after alarm reporting, arm/disarm bell squawk, urgency onentry delay, "quick exit", programmable transmission delay by zone, andtransmission delay on AC failure, TLM trouble, low battery, recent closecode, and cross zone police code, 

The system shall have stay/away and stay arming capability to allowthe user to remain on the premises while the system is armed. A quick-armfeature shall allow users without access codes to arm the system and exit.A door chime feature shall cause the keypad to beep when a selected dooris opened or closed. 

The system shall support any combination of up to 8 "Dual-Language"and "LED" type keypads with backlit displays. Keypads shall be surfacemounted and capable of fully programming and operating the system. Eachkeypad shall be assignable to operate the entire system. Dual-Languagekeypads shall be complete with 32 character liquid crystal display (LCD)to provide plain language programming instructions, operating instructions,and display of all alarms and supervisory conditions. They shall be capableof toggling between languages by pressing a keypad key combination. LEDkeypads shall have 8 zone indicators. All keypads shall have keypad activatedemergency alarms for panic, emergency, fire, and duress; 5 programmablefunction keys or programmable keypad functions; LED indicators for Ready,Armed, and Trouble or System; and shall be equipped with a Piezo Buzzerto provide audible feedback for correct key entries, pre-alert, and trouble. 

Each keypad shall have one zone input to allow a zone detector to bewired directly to the keypad. 

System shall support wireless operation with up to 8 wireless panicpendants, 16 wireless arm/disarm keys, and 4 wireless handheld keypads. 

The system shall allow 39 access codes including 32 user codes, 1 mastercode, 2 duress codes, 2 supervisor codes, 1 installer code, and 1 maintenancecode. The system shall be uploadable/downloadable to allow programmingand operation from a directly connected local computer, or from a remotecomputer over a telephone line or LINKS cellular communications equipment.Remote access shall be controlled by the owner to prevent unauthorizedaccess. 

The system shall support a 300, 1200, 2400 or 4800 bps serial printerconnected to the communications bus up to 1,000 feet (330m) from the controlpanel. The printer shall log all system events and transactions with timeand date stamp. Information shall be stored in the system's 128 event bufferwhich can be examined from the LCD keypad or via DLS software. 

The system shall meet UL standards as required for type of application. 

 